What is the difference between an ATS and an MTS?
An automatic transfer switch uses controls to change between supplies when the agreed conditions are met. A manual transfer switch needs an operator to make the changeover. Both require a suitable switching arrangement for the installation. Choose around the acceptable interruption, staff availability and operating plan, as well as cost.
Does an ATS provide uninterrupted power?
An ordinary open-transition ATS does not. It disconnects one source before connecting the other, and a standby generator also needs time to start and establish a suitable supply after a mains failure. Loads that cannot tolerate that interruption may need a UPS or a separately engineered continuity solution.
What size transfer switch do I need for my generator?
Start with the maximum current through the switch in both mains and generator operation, supply voltage and phase, and the load characteristics. Then check the utilisation duty, ambient conditions, fault level, protection coordination and cable terminations. Generator kVA alone is not enough to select a panel.
Do I need a 3-pole or 4-pole transfer switch?
The neutral and earthing design determines whether the neutral needs to be switched. Three-phase equipment may use different arrangements, and TPN describes a three-phase-and-neutral supply rather than proving that the neutral is switched. Have the proposed pole arrangement checked against the complete installation.
Can I fit an ATS to an existing diesel generator?
Potentially. FW Power can review the generator controller, remote-start interface, voltage, frequency, protection and existing installation. Send the generator model and controller details with your enquiry. A motorised changeover switch on its own is not necessarily a complete automatic transfer system.
Can a manual changeover switch be used with a temporary generator?
Yes, where the complete installation is designed for that purpose. The inlet or connection arrangement, source separation, earthing, protection and operating procedure all need review. An MTS alone does not provide automatic generator starting or automatic fault response.
Are UK-manufactured transfer switch panels available?
FW Power can discuss UK-manufactured ATS and MTS panel options. The build specification, switching components, enclosure, controls, documentation and lead time are confirmed for the proposed package. Photographs show examples of ATS panels; they do not establish the specification or availability of every option in the selector.
Can you quote for a bespoke ATS or MTS panel?
Yes. Include your single-line diagram if available, load current, supply arrangement, installation environment, cable details, space constraints and required functions. Tell us about any bypass, remote indication or special project requirements so our team can review the scope before quotation.